Fluke 1507/1503 Insulation Testers
Features and benefits • Insulation test range: 1507 - 0.01 M Ω to 10 G Ω; 1503 - 0.1 M Ω to 2000 M Ω • Insulation test voltages: 1507 - 50 V, 100 V, 250 V, 500 V, 1000 V; 1503 - 500 V, 1000 V • Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio • Make repetitive tests simple and easy with the 1507’s Compare (Pass/Fail) function (only available on the 1507) • Repetitive or hard-to-reach testing is easy with the remote test probe • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection • Auto-discharge of capacitive voltage for added user protection • AC/DC voltage: 0.1 V to 600 V • 200 mA Continuity • Resistance: 0.01 Ω to 20.00 K Ω • Save battery power with auto power off • Read measurements easily with large, backlit display • CAT IV 600 V overvoltage category rating for added user protection • Remote probe, test leads, probes and alligator clips included with each tester • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work • Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests • One-year warranty
1507/1503 Specifications
AC/DC voltage measurement
Range | Resolution | Accuracy | 50 Hz to 400 Hz | | ± (% of Rdg + Digits) | 600.0 V | 0.1 V | ± (2 % + 3) |
Input impedance: 3 M Ω (nominal), < 100 pF Common mode rejection ratio (1 kW unbalanced): > 60 dB at dc, 50 or 60 Hz Overload protection: 600 V rms or dc
Earth bond resistance measurement
Range | Resolution | Accuracy | | | 1 + (% of Rdg + Digits) | 20.00 Ω | 0.01 Ω | ± (1.5 % + 3) | 200.0 Ω | 0.1 Ω | ± (1.5 % + 3) | 2000 Ω | 1 Ω | ± (1.5 % + 3) | 20.00 k Ω | 0.01 k Ω | ± (1.5 % + 3) |
1 Accuracies apply from 0 to 100 % of range.
Overload protection: 2 V rms or dc Open circuit test voltage: > 4.0 V, < 8 V Short circuit current: > 200.0 Ma
Accuracy (Model 1507)
Output Voltage | Display Range | Resolution | Test Current | Accuracy | | | | | ± (% of Rdg + Digits) | 50 V | 0.01 M Ω to 20.00 M Ω | 0.01 M Ω | 1 mA @ 50 k Ω | ± (3 % + 5) | (0 % to + 20 %) | 20.0 M Ω to 50.0 M Ω | 0.1 M Ω | 1 mA @ 50 k Ω | ± (3 % + 5) | 100 V | 0.01 M Ω to 20.00 M Ω | 0.01 M Ω | 1 mA @ 100 k Ω | ± (3 % + 5) | (0 % to + 20 %) | 20.0 M Ω to 100.0 M Ω | 0.1 M Ω | 1 mA @ 100 k Ω | ± (3 % + 5) | 250 V | 0.01 M Ω to 20.00 M Ω | 0.01 M Ω | 1 mA @ 250 k Ω | ± (1.5 % + 5) | (0 % to + 20 %) | 20.0 M Ω to 200.0 M Ω | 0.1 M Ω | 1 mA @ 250 k Ω | ± (1.5 % + 5) | 500 V | 0.01 M Ω to 20.00 M Ω | 0.01 M Ω | 1 mA @ 500 k Ω | ± (1.5 % + 5) | (0 % to + 20 %) | 20.0 M Ω to 200.0 M Ω; 200 M Ω to 500 M Ω | 0.1 M Ω; 1 M Ω | 1 mA @ 500 k Ω; 1 mA @ 500 k Ω | ± (1.5 % + 5); ± (1.5 % + 5) | 1000 V | 0.1 M Ω to 200.0 M Ω | 0.1 M Ω | 1 mA @ 1 M | Ω ± (1.5 % + 5) | (0 % to + 20 %) | 200 M Ω to 2000 M Ω; 2.0 G Ω to 10.0 G Ω | 1 M Ω; 0.1 G Ω | 1 mA @ 1 M Ω; 1 mA @ 1 M Ω | ± (1.5 % + 5); ± (10 % + 3) |
Accuracy (Model 1503)
Output Voltage | Display Range | Resolution | Test Current | Accuracy | | | | | ± (% of Rdg + Digits) | 500 V | 0.1 M Ω to 20.00 M Ω | 0.01 M Ω | 1 mA @ 500 k Ω | ± (2.0 % + 5) | (0 % to + 20 %) | 20.0 M Ω to 200.0 M Ω; 200 M Ω to 500 M Ω | 0.1 M Ω; 1 M Ω | 1 mA @ 500 k Ω; 1 mA @ 500 k Ω | ± (2.0 % + 5); ± (2.0 % + 5 | 1000 V | 0.1 M Ω to 200.0 M Ω | 0.1 M Ω | 1 mA @ 1 M Ω | ± (2.0 % + 5) | (0 % to + 20 %) | 200 M Ω to 2000 M Ω | 1 M Ω | 1 mA @ 1 M Ω | ± (2.0 % + 5) |
1507/1503 General Specifications • Maximum voltage applied to any terminal: 600 V ac rms or dc • Storage temperature: -40 °C to 60 °C (-40 °F to 140 °F) • Operating temperature: -20 °C to 55 °C (-4 °F to 131 °F) • Temperature coefficient: 0.05 x (specified accuracy) per °C for temperatures < 18 °C or > 28 °C (< 64 °F or > 82 °F) • Relative humidity noncondensing: 0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F); 0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F); 0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F) • Vibration: Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument • Shock: 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) • Electromagnetic compatibility: In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) • Safety: Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) • Certifications: CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition • Batteries: Four AA batteries (NEDA 15A or IEC LR6) • Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MW with a duty cycle of 5 seconds on and 25 seconds off. • Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 W with a duty cycle of 5 seconds on and 25 seconds off. • Size: 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L) • Weight: 550 g (1.2 lb) • IP rating: IP40 • Operating: 2000 m CAT IV 600 V, 3000 m CAT III 600 V • Non-operating (storage): 12,000 m • Over-range capability: 110 % of range
Included accessories • TL224 Test Leads • TP74 Test Probes • Clips PN 1958654 (red) and PN 1958646 (black) • Holster • Remote probe
|
|
|
|