Product Search:

  

Search for:

 


Product

Additional Photos

Belden 1069A Paired - 600V Tray Cable

 

Conductor
• Number of Pairs - 2
• Total number of Conductors - 4
• AWG - 16
• Stranding - 7x24
• Conductor Material - BC (Bare Copper)

Insulation
Insulation Material - PVC/Nylon (Polyvinyl Chloride/Nylon)
Pair Color Code Chart

NumberColor
1Black & White and Numbered 1
2Black & White and Numbered 2

Overall Cabling

• Overall Cabling Lay Length - 4.93 in.

Outer Shield
• Outer Shield Material Trade Name - Beldfoil
• Outer Shield Type - Tape
• Outer Shield Material - Aluminum Foil-Polyester Tape
• Outer Shield % Coverage - 100%

Outer Shield Drain Wire
• Outer Shield Drain Wire AWG - 16
• Outer Shield Drain Wire Stranding - 7x24
• Outer Shield Drain Wire Conductor Material - TC (Tinned Copper)

Outer Jacket
• Outer Jacket Material - PVC (Polyvinyl Chloride)
• Outer Jacket Nominal Wall Thickness - .047 in.
• Outer Jacket Ripcord - Yes

Overall Nominal Diameter
• Overall Nominal Diameter - .456 in.

Mechanical Characteristics
• Wet Temperature Range - -30°C To +75°C
• Dry Temperature Range - -30°C To +90°C
• Bulk Cable Weight - 90.3 lbs. / 1000 ft.
• Max. Recommended Pulling Tension - 179 lbs.
• Min. Bend Radius (Install) - 4.6 in.

Applicable Standards
• NEC/(UL) Specification - NPLF, TC, UL 1277
• EU RoHS Compliant (Y/N) - Yes
• EU RoHS Compliance Date (mm/dd/yyyy) - 4/1/2005
• Other Specification ICEA S-73-532, S-61-402 - ICEA S-73-532, S-61-402

Flame Test
• UL Flame Test - UL1685 UL Loading
• C(UL)Flame Test - FT4
• IEEE Flame Test - 1202
• ICEA Flame Test - T-29-520

Suitability
• Suitability (Burial) - Yes
• Sunlight Resistance - Yes

Plenum/Non-Plenum
• Plenum (Y/N) - N

Electrical Characteristics
• Nom. Characteristic Impedance - 49 Ohms
• Nom. Mutual Capacitance @ 1KHz - 40 pF/ft.
• Nom. Conductor DC Resistance @ 20 Deg. C - 3.67 Ohms/1000 ft.